Expandable up to 4 loops with full support of
Apollo (S90, XP95, Discovery) and Hochiki ESP protocols.
|
 |
Advanced graphical LCD user interface with up
to 1000 fire zones as standard, allowing full EN54 compliance without
additional hardware or LED indication. |
 |
5 Amp (70V - 230V) power supply and charger
to EN54 part 4. |
 |
Removable equipment chassis with plug-in
connectors for simple fixing and cable termination. |
 |
Fully on-site programmable via on-board
alphanumeric keypad or PC configuration tools. |
 |
Dedicated system and navigation keys for
simple user control. |
 |
User-friendly Windows based PC-NeT
configuration software includes virtual panel remote diagnostics
functionality via a low modem connection. |
 |
500 mA available loop current for
un-compromised connection of loop driven sounders and other field devices.
|
 |
Dedicated connection for optional on-board
printer. |
 |
Dual flash based microprocessor technology
with on-boardReal Time Clock. |
 |
Powerful cause and effect programming coupled
with flexible ‘Dynamix’ zoning makes the panel suitable for a wide
range of system applications including the most complex multi area systems.
|
 |
Installer friendly ‘Self-learn’ and
'Automatic Loop Detection' facility for uncomplicated, trouble-free,
commissioning and fault finding. |
 |
Advanced Day/night facilities with multiple
programmable 7-day timers. |
 |
Contamination, Sensitivity Band selection and
Rapid Drift Compensation (protocol dependant). |
 |
The Mx-4400 can be easily networked
with any other Mx-4000 series panel or peripheral.
|
 | The Mx-Network
operates as a true peer-to-peer, fault tolerant system with full cross panel
cause and effect functionality of up to 1000 zones. |
 |
Flash memory and the
advanced graphical display enables the panels to be configured to operate in
virtually any language and allows the installers logo and company details to
be applied the LCD display. |
 |
‘Trace’
diagnostics feature enables highly accurate device monitoring with event
tracing and load monitoring of all loop, sounder and auxiliary outputs.
|
| Base
Technology |
Dual
Flash based Processors with Real Time Clock, Trace diagnostics,
PuLsE communications & programmable languages |
| Display |
Backlit
240 x 64 Graphical Display |
| LED
Indicators |
3 Red (2
x Fire, 1 x Alarm), 1 Green (Power) & 12 Amber (Fault & System) |
| Controls |
Alpha
Numeric Keypad, Navigation Keys & System Keys for Reset, Mute,
Silence/Resound & Evacuate |
| Protocols |
Hochiki
ESP, Apollo XP95 and Discovery |
| Number of
Fire Zones |
1000
'Dynamix' |
| Number of
Loops |
0 - 4.
Expandable via individual plug-in loop driver |
| Devices
per Loop |
As per
Detector Manufacturer's Specifications |
| Loop
Current |
500 mA |
| On Board
Sounder Circuits |
4 x 1 Amp
programmable |
| On Board
Relays |
2 x 1 Amp
30V AC/DC Programmable |
| Auxiliary
Supply |
1 x 24V
300mA Switchable |
| Open
Collector / Logic Outputs |
8 x
Programmable |
|
Programmable Switch Inputs |
8 Volt
Free Digital Inputs with flexible programming |
| On Board
Power Supply |
5 Amp
High Efficiency Switched Mode with PFC |
| Mains
Supply |
70V - 230
V 50 Hz AC (+10%, -15% tolerance) 1.7 Amp |
| Battery
Capacity |
24V 18Ah
internal. 24V 48Ah external. |
| Charger
Current |
1.6 Amp
DDP monitored, temperature compensated internal charger |
| Serial
Ports |
1 RS232
Onboard for PC, Modem or Dedicated Printer |
|
Programming |
Via
on-board Keypad or PC running Windows Tools |
| Event Log |
1000 Fire
& Event + Diagnostic |
|
Networking |
Optional
plug in Network card |
| Printer
(Option) |
Dedicated
port for optional integral serial printer |
| Enclosure |
Steel
IP40 |
| Cable
Entry |
20mm
Knock-outs. 18 x top, 9 x top rear and 2 bottom |
| Colour |
Beige
(textured) |
|
Dimensions H x W x D mm |
475 x
450x 115 |
| Weight |
10.5Kg |
| Metalwork
Options |
Flushing
Bezel, Ancilliary Enclosure and Battery Box |
| Standards |
Designed
to comply with EN54 parts 2/4 |