The Concept panel has been designed to work with the new Fulleon 2 wire sounders, which operate on the detection zone using standard call points and detectors. The panels are available in 2. 4. 6. 8, 12, and 24 zone models with 2 or 4 sounder circuits. They can be used in conventional 4 wire mode, e.g. a pair for detectors and a pair for sounders, for use with existing systems, and also in a 2 wire mode by adding a 2 wire sounder on to the zone. They can be used with a combination of both.      

Concept 12 Zone Concept 2 Zone
concept_big_noborder.jpg (10524 bytes) concept_small_noborder.jpg (11122 bytes)

The 2 wire system reduces the installation costs dramatically, as cabling consists of just 2 wires and is therefore cheaper. The number of terminations are less and if the sound level is found to be too low on final commissioning, additional sounders can be added easily.

Concept 24 Zone

bulletMeets BS5339 part 4 and EN54.
bulletIntegral detector removal monitoring indicated zonally using
schotky diode in detector base .
bulletSuits Apollo and Hochiki detectors.
bullet3 auxiliaries: I fault, 1 silence on silence, I silence on reset.
(2 on the 2 zone).
bullet2amp integral power supply (lamp on the 2 zone).
bulletSuitable for up to 7AH batteries (1.2AH on the 2 zone).
bulletEarth fault monitoring.
bulletLow voltage battery protection.
bulletRepeater outputs.
bulletReset, silence, evacuate inputs.
bulletPrecinct/class change input.
bulletOne man test facility.
bulletIsolation of zones, relay, sounders and inputs
(zones and sounders only on the 2 zone).

These panels are designed to comply with BS5839 and EN 54. The panel consists of two printed circuit boards; one contains the zones and sounders and the other the power supply. The power supply is rated at 2amps,'Monitors battery voltage and has a built-in low voltage battery protect relay to prevent deep discharge. The main board has connections for zones 2 or 4 standard sounder circuits, fully monitored, and remote evacuate or class changes, together with three auxiliaries, one for fault, one for alarm - reset on silence, one for alarm - reset on reset. It also has a full set or repeater connections, including remote evacuate, silence and reset. Each zone is monitored for open circuit, short circuit detector head removal using no more than a resistor at end of line. The zones can also support the new Fulleon 2 wire sounder which can be signalled from the panel to turn off and on. Each zone is separately fused for sounder operation. Failure of the fuse does not affect zone monitoring. As well as displaying all faults on the front of the panel it is also possible to isolate zones individually, sounders, auxiliaries and remote input, and also to perform one man test operation, all from the front controls. The panel is also provided with a number of internal switching features to enable, for example, 1998 (short circuit for fire) operation, zone I and 2 non latching facilities, delayed sounders and detector remove one man test operation.

Concept 4 Zone

conceptsmall4small.jpg (8598 bytes)

Concept Repeater

 

 

Concept Specials

Concept_glass_noborder.jpg (11376 bytes)

2-12 Zone - 300mm high x 350mm wide x 85mm deep
1-2 Zone - 260mm high x 240mm wide x 65mm deep
bulletMetal cabinet with lift off front door with knockout at
top and bottom.
bulletFitted with lock and enable key.
bulletPower supply 240v 5OHz input. 12 zone current limited
to 2amps for a maximum of 2 x 7AH batteries.
bullet2 zone current limited to lamp for a 2 x 1.2AH batteries.
 