FireSense - Fire Detection Equipment

Fire Panels   Technical Information


Home
Products
Fire Panels
Addressable
Power Supplies
Full Range
Contact Us

Links
Technical

Addressable Fire Panels

Smoke Detectors

Sounders

......

 

ZXR4 and ZXR5 REPEATERS

-    Compatible With ZXa And ZXe Intelligent Multi Protocol Fire Alarm Control Panels
-    Connects To The Peripheral Bus (RS485)
-    Passive And Active Repeater Options
-    Back-Lit LCD Display Provides 2x4O Characters
-    For Event And Location Information
-    Six General System Status LEDS
-    Controls For System Reset, Accept/Mute, Silence/Resound And Sound Alarms (Active Repeater Only)
-    "Access Enable" Key-Switch Active Repeater Only
-   Up To 31 Active Or Passive Repeaters Can Be Connected To A Peripheral Bus

repeaters.jpg (7844 bytes) The ZXa/ZXe Repeaters are compact remote 1/0 device for the ZXa and ZXe intelligent multi protocol fire alarm control panels. These units, along with other remote 1/0 devices and the external printer provide a complete range of peripheral devices to further enhance the functionality and expendability of the ZXa/ZXe intelligent multi protocol fire alarm control panels.

The Repeaters provide an extension to the operation of the Fire Alarm Control Panels. There are two types available; the passive Repeater and the active Repeater. Both types display the operational state of the panel using the 2x4O LCD and the six common status LED indicators (Power, Fault, Accepted, Silenced, Disabled, Fire). In addition to the panel status indication, the Full Repeater is equipped with a key operated "Access Enable" switch and can also control the panel using the SYSTEM RESET, MUTE/ACCEPT, SiLENCE/RESOUND, and SOUND ALARMS functions. The repeaters are connected to the ZXa/ZXe control panels via the RS485 peripheral port (Port D). An RS485 communication card must be fitted in the ZXa or ZXe intelligent multi protocol fire alarm control panel for that purpose. The panel supervises the Active Repeater whereas the Passive Repeater is a display-only device and is not supervised by the panel. In case of a communication failure both annunciators will indicate a system fault whereas the panel will indicate only a communication failure with an Active Repeater. The repeaters require an external power supply to operate. Power may be taken from the auxiliary power supply output on the ZXa/ZXe or any other suitable DC supply of suitable voltage and current rating listed for fire protection use. The RS485 peripheral address is set via an onboard DIP switch. Other peripherals can be daisy chained on the same line. Up to a maximum of 31 Active or Passive Repeaters can be connected on a peripheral bus.

_________________________________________________
| Home | Products | Technical | Contact Us |
© Copyright 2007 FireSense Ltd UK
Last updated 13/02/07