Baldwin Boxall BVOC4M

In stock
Product Code
BVOC4M
SKU
BB1804M

Baldwin Boxall Omnicare 4-Way Loop Wired Control Panel

OmniCare Loop Wired EVC System - 4 Way Panel

DELIVERY

We always aim to same day dispatch on all orders received before 2.30pm.

Read more about our delivery policy

TRADE COUNTER

Firesense also offer the ability to collect your order from our trade counter. 

Read more about our trade counter

Baldwin Boxall BVOC4M

Communication when you need it most

OmniCare EVC system is a Loop Wired Emergency Voice Communication system which features Disabled Refuge (standard and Advance options – Type B), Fire Telephone (Type A), Combined Refuge/Fire Telephone Outstation (Type C), Steward Telephone (Type A) and Emergency Assistance/Disabled Toilet Alarm facilities. Fully expandable, it enables up to 127 outstations per system.

Emergency Voice Communication (EVC) systems provide two-way communication between building management or emergency services and people inside a building who require assistance with evacuation in an emergency. Communication is made between a central location point and a number of points known as ‘outstations’ located around a building or building complex.

The OmniCare system was the first of its kind when introduced as a combined EVC system. Since then it has been installed throughout the world becoming the system of choice for many. The system includes a three-part toilet alarm kit option which, like all of the remote units, is powered from the line (no local power is required).

OmniCare provides an alternative EVC option to our popular radial-wired CARE2 EVC system.

Further Information

  • The OmniCare standard system has a capacity for up to 127 outstations in total (either connected to a single control panel or on a networked system with multiple control panels).
  • Touchscreen control is available and ideal for use in public/reception and lobby areas, providing full control of the OmniCare system via a bespoke button or graphical display.
  • Disabled refuge, advance disabled refuge, fire telephone, emergency/steward telephone, combined DRS/fire telephone and emergency assistance/toilet alarm units can be placed on the same loop.
  • Multiple Control Panels can be included on a single system (configured as a Master and Slave units).
  • Control Panels, Type A, Type B and Type C outstations are supplied surface-mountable as standard and flush-mountable with separately available bezel.
  • Addressable system via the outstation with speech steered (Type B Disabled Refuge) and full duplex speech (Type A Fire/Steward Telephone) communication.
  • The system is fully monitored and battery backed.
  • Standard battery backup provides 24 hours standby plus three hours use in the event of a mains failure as standard. Increased capacity is possible, if required. (A separate box to house batteries is supplied with panels larger than 32-way).
  • Link to fire detection system prevents hoax calls from disabled refuge (toilet alarms and fire telephones remain active). Can be completely or partly overridden. Outstations are kept in ‘standby mode’ until activated. For system maintenance and testing an override switch (BVCRBG) should be connected to the system.
  • Fully BS9999:2017, BS5839-9:2021 and BS8300-2:2018 compliant when installed according to the standards.
    For systems that require more field devices please refer to our OmniCarePLUS solution. Or, if the OmniCare EVC System is not what you are looking for, our CARE2 Radial Wired EVC System may suit your requirements.

Panel Features

  • Grey finish (BVOC04M). Also available in stainless steel (BVOC04MS).
  • Surface mounting unit (can be flush mounted using a bezel  - product code BVCRFB2). Rack mounting kit available (BVCRM3).
  • Lockable glazed door.
  • Handset volume control and ‘listening’ facility.
  • Output for unanswered call indicator; with adjustable delay. (Remote lamp/buzzer available - code BVOCCA.)
  • Indicators for: in use/occupied, call, fault, power, charger and speech volume.
  • Volt free contact - operated when in fault, set during installation.

Omnicare System Features

  • Multiple master/slave panels can be linked in one system.
  • Full system monitoring.
  • Choice of outstations, including emergency assistance alarms (addressable via the remote unit).
  • Link to fire detection system prevents hoax disabled refuge calls (emergency assistance alarms and fire telephones remain 
    active). Can be completely or partly overridden.
  • Speech steered (disabled refuge remotes) and full duplex speech (fire telephones and emergency telephones).
  • Battery backed for use in the event of mains power failure (24 hours in standby plus three hours use, as standard. These times can be increased if required. Please contact our Sales Department for advice).  
  • Wired in a loop configuration. (Please refer to our separate cabling information leaflet.)

General System Information

  • There are two main components - the master control panel(s) and the remote units.
  • Remote units are wired in a ring circuit configuration and are ‘self-learning’, with an auto-commissioning feature.
  • The ring circuit technology enables continued operation in the event of a cable break.
  • Any combination of remote units can be linked to the control panel on a single wiring loop.
  • The master control panel is typically wall mounted in a central control room.
  • Remote units are wall mounted in locations such as refuge areas, stairwells, fallback positions, corridors and other ‘gathering’ points, at a height easily reached by users.
  • More than one master panel can be placed on the ring circuit, thus allowing control of local areas
Attributes
Approval BS5839-9:2021
Category Type Panel
Channels 4
Colour Grey
Clearance No
Write Your Own Review
You're reviewing:Baldwin Boxall Omnicare 4-Way Loop Wired Control Panel
Your Rating

Specifications

Power supply
230V AC
Power consumption (VA)
10VA + 1VA per remote handset fitted
Humidity range 95% non-condensing
Temperature range -10°C to +30°C
Indicators In use, call, fault, power, charger and speech volume
Remote signalling of fault Volt-free contact, closing/opening (set on commissioning)
Dimensions mm W x H x D  410 x 290 x 200
Bezel dimensions mm W x H (radius)  461 x 340 (25)
Bezel cut out mm 420 x 300
Knockouts/cable entry points  20mm diameter top & rear
Mounting position  Vertical centre of controls should be at a height of 1.4-1.5m (BS5839-9)
Batteries supplied as standard 1 x pair BY7.2 (7.2 Amp/Hr)
Weight 9.16 kg
Finish RAL 7038