Baldwin Boxall BVOCECPS

In stock
Product Code
BVOCECPS
SKU
BB1810S

Baldwin Boxall Omnicare Disabled Refuge Stainless Steel Remote Outsation

Disabled Refuge Green Remote

DELIVERY

We always aim to same day dispatch on all orders received before 2.30pm.

Read more about our delivery policy

TRADE COUNTER

Firesense also offer the ability to collect your order from our trade counter. 

Read more about our trade counter

Baldwin Boxall BVOCECPS

Communication when you need it most

OmniCare EVC system is a Loop Wired Emergency Voice Communication system which features Disabled Refuge (standard and Advance options – Type B), Fire Telephone (Type A), Combined Refuge/Fire Telephone Outstation (Type C), Steward Telephone (Type A) and Emergency Assistance/Disabled Toilet Alarm facilities. Fully expandable, it enables up to 127 outstations per system.

Emergency Voice Communication (EVC) systems provide two-way communication between building management or emergency services and people inside a building who require assistance with evacuation in an emergency. Communication is made between a central location point and a number of points known as ‘outstations’ located around a building or building complex.

The OmniCare system was the first of its kind when introduced as a combined EVC system. Since then it has been installed throughout the world becoming the system of choice for many. The system includes a three-part toilet alarm kit option which, like all of the remote units, is powered from the line (no local power is required).

OmniCare provides an alternative EVC option to our popular radial-wired CARE2 EVC system.

Further Information

  • The OmniCare standard system has a capacity for up to 127 outstations in total (either connected to a single control panel or on a networked system with multiple control panels).
  • Touchscreen control is available and ideal for use in public/reception and lobby areas, providing full control of the OmniCare system via a bespoke button or graphical display.
  • Disabled refuge, advance disabled refuge, fire telephone, emergency/steward telephone, combined DRS/fire telephone and emergency assistance/toilet alarm units can be placed on the same loop.
  • Multiple Control Panels can be included on a single system (configured as a Master and Slave units).
  • Control Panels, Type A, Type B and Type C outstations are supplied surface-mountable as standard and flush-mountable with separately available bezel.
  • Addressable system via the outstation with speech steered (Type B Disabled Refuge) and full duplex speech (Type A Fire/Steward Telephone) communication.
  • The system is fully monitored and battery backed.
  • Standard battery backup provides 24 hours standby plus three hours use in the event of a mains failure as standard. Increased capacity is possible, if required. (A separate box to house batteries is supplied with panels larger than 32-way).
  • Link to fire detection system prevents hoax calls from disabled refuge (toilet alarms and fire telephones remain active). Can be completely or partly overridden. Outstations are kept in ‘standby mode’ until activated. For system maintenance and testing an override switch (BVCRBG) should be connected to the system.
  • Fully BS9999:2017, BS5839-9:2021 and BS8300-2:2018 compliant when installed according to the standards.
  • For systems that require more field devices please refer to our OmniCarePLUS solution. Or, if the OmniCare EVC System is not what you are looking for, our CARE2 Radial Wired EVC System may suit your requirements.

Benefits& Features

  • Provides two-way, hands free, speech steered communication.
  • Self-powered from ring circuit, no local power source is required. Automatic battery backup is provided by the control panel in the event of a mains power failure.
  • Green finish (also available in stainless steel BVOCECPG).
  • Addressable unit.
  • Volt free contact, active when occupied. To operate over door lamps, silence speaker/sounder, etc.
  • Stainless steel ‘press to call’ button.
  • Option to be permanently ‘active’ if required.
  • Reset from either remote unit using the key switch or via the master control panel.
  • All outstations are in a loop circuit from control panel(s).
  • A link to the fire detection system prevents hoax disabled refuge calls. This feature can be completely, or partly, overriden.
  • Surface mounting unit (can be flush mounted using a bezel).
Attributes
Approval BS5839-9:2021
Category Type Outstation
Colour Stainless Steel
Clearance No
Write Your Own Review
You're reviewing:Baldwin Boxall Omnicare Disabled Refuge Stainless Steel Remote Outsation
Your Rating

Specifications

Product code 
BVOCECPG
Power supply
12-40V DC self powered from ring circuit
Power consumption (VA)
 30mA @ 35V typical
Humidity range 95% non-condensing
Temperature range -10°C to +40°C
Indicators System healthy, status
Finish Stainless steel grade 304
Dimensions mm W x H x D  134x134x56
Bezel dimensions mm W x H (radius)  154x154x(10)
Bezel cut out mm 136x136
Knockouts/cable entry points  7 (20mm & 26mm)
Mounting position  Refuge remotes should be placed at a height of 900mm to 1.2m
Weight 1.06kgs
IP65 rated enclosure (available separately)
Dimensions mm WxHxD  200 x 200 x 80
Plasterboard back box (available separately)
Dimensions mm WxHxD 131 x 142 x 65
Cutout dimensions mm WxHxD 132 x 143