We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
C-TEC CAST-PRO CO Fire & Smoke & Heat Multisensor c/w Tone Sounder & C-3-9.4 White VAD
CAST-PRO CO fire, heat & smoke multisensor sounder VAD detector
DELIVERY
We always aim to same day dispatch on all orders received before 2.30pm.
TRADE COUNTER
Firesense also offer the ability to collect your order from our trade counter.
- Multiple functionality in a single device – CO fire, heat & smoke multisensor fire detection plus a 92db(A) tone Alarm sounder and a C-3-9.4 VAD – detects real fires quickly, reduces false alarms effectively and indicates true alarm conditions decisively.
- Certified to EN54-3, 5, 7, 13, 17, 23, 29 & 31 by Kiwa Telefication.
- Compatible with C-TEC’s ZFP and XFP CAST protocol addressable fire panels.
- MASC™ (Miniature Advanced Smoke Detection Chamber) and AFFIRM™ algorithms provide incredible tolerance to false alarms whilst enhancing the detection of real fire conditions.
- Drift compensation functionality.
- Onboard short circuit loop isolator.
- Includes two 8mm x 2mm ultra-bright red LED indicating strips.
- Multiple detection modes and different sensitivities for different times of the day.
- 13.2mA max. alarm current (max vol, VAD on).
- 630uA typical quiescent current @ 22-40V DC.
- Compatible with C-TEC’s CA408 CAST base c/w integrated locking mechanism & ID tag.
| Category Type | Detector Sounder Visual Alarm Device |
|---|---|
| Colour | White |
| Detection | Multisensor Heat & CO |
| IP Rating | IP21C |
| System Type | Addressable |
| Clearance | No |
Approvals/certifications
Compatibility
Type
Sensitivity
Supply Wiring
Supply/operating voltage
Quiescent current
Alarm current (lmax at Vmin)
Alarm current (lavg at Vmin)
Sound pressure level (LAFmax) at Vmax at 1m
VAD category & Coverage
Indicators
Connections
Dimensions
IP rating
Weight
Operating conditions/temperature
Notes
EN54-13 by Kiwa Telefication, CPR 0063-CPR-212190016, Kiwa Telefication certified to EN54-3, 5, 7, 17 ,23 ,29 & 31
C-TEC's XFP/ZFP CAST Protocol addressable fire panels
CO, Heat & Smoke Fire Detection plus Tone Alarm & White VAD
12 detection modes (default for this device is mode 10)
2-wire, polarity sensitive
28V to 40V DC
630uA @40V
13.2mA (max volume, VAD lit)
10.8mA (max volume, VAD lit)
92dB(A)
C-3-9.4 (10m2/mA efficiency; 0.5Hz Synchronised)
2 LED indicator strips, emitting red light when in alarm offering 360° visibility. Optional remote LED
Via CA408 base: 1 +Ve IN (analogue switch); 2 +Ve OUT (analogue switch); 3 Remote LED +Ve; 4 0V; 5 0V; 6 Screen; 7 Screen
105mm Diameter x 51mm deep (detector only); 105mm diameter x 68mm deep (detector in base)
IP21C
133g (not in base); 188g (in base)
-10°C to +50°C. Max relative humidity: 95% (non condensing)
Requires a CA408 CAST base. CA408R relay base also available)
| Approvals/Certifications | EN54-13 by Kiwa Telefication, CPR 0063-CPR-212190016, Kiwa Telefication certified to EN54-3, 5, 7, 17 ,23 ,29 & 31 |
| Compatibility | C-TEC's XFP/ZFP CAST Protocol addressable fire panels |
| Type | CO, Heat & Smoke Fire Detection Plus Tone Alarm & White VAD |
| Sensitivity | 12 detection modes (default for this device is mode 10) |
| Supply Wiring | 2-wire, polarity sensitive |
| Supply/operating voltage | 28V to 40V DC |
| Quiescent current | 630uA @40V |
| Alarm current (lmax at Vmin) | 13.2mA (max volume, VAD lit) |
| Alarm current (lavg at Vmin) | 10.8mA (max volume, VAD lit) |
| Sound pressure level (LAFmax) at Vmax at 1m | 92dB(A) |
| VAD category & Coverage | C-3-9.4 (10m2/mA efficiency; 0.5Hz Synchronised) |
| Indicators | 2 LED indicator strips, emitting red light when in alarm offering 360° visibility. Optional remote LED |
| Connections | Via CA408 base: 1 +Ve IN (analogue switch); 2 +Ve OUT (analogue switch); 3 Remote LED +Ve; 4 0V; 5 0V; 6 Screen; 7 Screen |
| Dimensions | 105mm Diameter x 51mm deep (detector only); 105mm diameter x 68mm deep (detector in base) |
| IP Rating | IP21C |
| Weight | 133g (not in base); 188g (in base) |
| Operating conditions/temperature | -10°C to +50°C. Max relative humidity: 95% (non condensing) |
| Notes | Requires a CA408 CAST base. CA408R relay base also available) |