C-TEC 8 Zone CFP Repeater Panel
8 Zone CFP Repeater Panel
DELIVERY
We always aim to same day dispatch on all orders received before 2.30pm.
TRADE COUNTER
Firesense also offer the ability to collect your order from our trade counter.
- Can be used to repeat the functions of a master CFP standard or AlarmSense 2-8 zone fire panel at remote parts of site (e.g. all potential fire service entrances).
- Up to 8 repeaters per CFP master.
- Includes its own Mains power supply that requires its own standby battery supply.
- Provides the user with access to all AL1 and AL2 functions.
- Master/Repeater communication achieved using CFP761 network driver cards (one CFP761 is supplied with the Repeater, an additional CF761 card is required at the master CFP).
- Communicates over screened two-wire fire resistant cable.
- Total repeater network cable length should not exceed 1KM.
- Attractive flush or surface mountable plastic lid and enclosure - no bezel required.
Can be used to repeat the functions of a master CFP standard or AlarmSense 2-8 zone fire panel at remote parts of site (e.g. all potential fire service entrances).
Features
- Up to 8 repeaters per CFP master.
- Includes its own Mains power supply that requires its own standby battery supply.
- Provides the user with access to all AL1 and AL2 functions.
- Master/Repeater communication achieved using CFP761 network driver cards (one CFP761 is supplied with the Repeater, an additional CF761 card is required at the master CFP).
- Communicates over screened two-wire fire resistant cable.
- Total repeater network cable length should not exceed 1KM.
- Attractive flush or surface mountable plastic lid and enclosure – no bezel required.
| Category Type | Repeater |
|---|---|
| IP Rating | IP30 |
| System Type | Conventional |
| Clearance | No |
Write Your Own Review
| Compatibility | Compatible with C-TEC's CFP Standard and CFP AlarmSense panels. Legacy CFP Economy panels cannot be extended with this product) |
| Mains Supply | 230V 50/60Hz |
| Internal power supply | 19V-28.5V (27V nominal) |
| Max battery size and type | 2 x 12V 2.1Ah VRLA connected in series for 72 hour standby. 2 x 12V 1.2Ah for 24 hours |
| Max network cable length | 1KM |
| Product dimensions (mm) | 380W x 235H x 96D (hole required for flush mounting = 367W x 220H x 75D. No bezel required) |
| Construction & finish | Plastic lid and base; RAL7035 textured |
| IP rating | IP30 |
| Weight | 1.75kg (without batteries) |
| Operating conditions/temperature | -5°C to +40°C. Max relative humidty; 95% |