We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
In stock
Product Code
EP212
SKU
CT8390
C-TEC Output Expansion Relay Board for EP203
Output Expansion Relay Board for EP203
DELIVERY
We always aim to same day dispatch on all orders received before 2.30pm.
TRADE COUNTER
Firesense also offer the ability to collect your order from our trade counter.
- An optional system expansion device for use with the EP203 three zone automatic extinguisher panel.
- Mounts inside the EP203 panel to provide five volt free relay contacts (reset, mode, discharged, hold and abort).
- Reset relay switches during the panel’s reset cycle.
- Mode relay switches when the extinguishant system’s mode is changed to manual.
- Discharged relay switches when a released flow switch input (e.g. from the extinguishant pipework) is received to indicate the extinguishant has been released.
- Hold relay switches when a hold input is received at the panel. If the panel is in 2nd stage alarm (i.e. it is in automatic mode and detection circuits are activated, or it is in either automatic/manual mode and a manual release input is operated) the extinguishant release sequence is halted.
- Abort relay switches when an abort input is received at the panel to cancel the extinguishant release sequence.
Category Type | Relay |
---|---|
Interface Type | Output |
System Type | Extinguishant |