8 zone fire alarm control panel for use with the Apollo Fire Detector's 'AlarmSense' range of 2 wire devices. Expandable to 12 zones, suitable for fully functional repeater panel
8 zone fire alarm control panel for use with the Apollo Fire Detector's 'AlarmSense' range of 2 wire devices. Expandable to 12 zones, suitable for fully functional repeater panel.
- 8 x AlarmSense zones
- Compatible with Apollo AlarmSense range of devices
- Activate controls via key switch or code entry
- Integral detector removal monitoring
- 3 Amp switch mode power supply Nom 27V DC
- 2 x conventional monitored sounder outputs
- 2 Aux C/O relays (1 x Fire) (1 x Fault). voltage free
- Class change I/P
- Alert I/P
- Fire & fault switched -ve outputs
- Test mode, with or without sounders
- Disable zones, sounder O/Ps, aux O/Ps & delays
- Conventional sounder circuits are fused @ 500mA with resettable fuses
- Fully functional repeater available
| Category Type | Panel |
|---|---|
| Colour | Grey |
| IP Rating | IP30 |
| System Type | Two Wire |
| Clearance | No |
Enclosure
Cable Entry
Dimensions
Mains Supply
Battery Capacity
Detection Zones
Sounder Circuits
On Board Relays
Outputs
Switch Inputs
Event Log
Non Priority Alarm
Coincidence Alarm
1.2mm Mild Steel IP30. Colour Ref: MW334E Interpon Powder coat
Via 20mm knockouts located in the top and rear of the cabinet
Back box: 450mm W x 300mm H x 85mm D, Lid: 460mm W x 310mm H x 25mm D
3A internal switch mode power supply, Nom 27V DC
8 x AlarmSense protocol EOL 3K3R
2 x conventional monitored fused @ 500mA EOL = 3K3R
1 x Fire, 1 x Fault, 3A, 30v volt free changeover
1 x Fire, 1 x Fault, 40mA switch -ve outputs
Class change & alert (Pulsing)
40 event history
Selectable per zone
Selectable per zone