Vox Ignis ViAC-WLI
The ViAC-WLI AquaCall Water Leak Interface is used to connect water leak detection cables and probes to a dedicated AquaCall water leak detection system or to add water leak detection sensors to any AssistCallPro safety alarm system. A dedicated AquaCall/AssistCallPro network can support up to 64 interfaces with associated detection, in any combination of cables and probes. Standalone 1-Zone and 4-Zone controllers can be used to connect one and four interfaces respectively. The AquaCall Water Leak Interface delivers maintenance free water leak detection as it use LV AC to drive the detection cable/probe. The AC does not corrode the probe (in water) unlike DC competitors. Supplied with ViAX-SBB-W white single gang backbox for surface mounting.
Detection Options
Each ViAC-WLI water leak interface plates can support 1 ViAC WLF feeder cable in lengths of 1.2m, 5m, or 10m and one of the following:
- Up to 50m of ViAC-WLD detection cable, available in lengths of 1m, 5m, and 10m, with a ViAC-WLE end-of-line device
- OR
- 1 ViAC-WLP detection probe on optional mounting bracket- no end-of-line device required.
Connections and Fixings
The ViAC-WLI interface can be connected to either a ViAC-1ZC or ViAC-4ZC using either 1mm CSA T&E / flex up to a distance of 500m or 2 pairs of Cat5/6 cable up to a distance of 100m
Technical summary
- White polycarbonate, single-gang device supplied with matching white backbox for surface mounting and cable entry.
- Connects to zone controller with up to 500m of 1mm twin core flex or 100m of Cat5/6 cable.
- Can be set to latching or non-latching operation via DIP switch.
- Powered by AssistCallPro system, requires no local power.
- Connects to detection cable or probe via a 1.2m, 5m or 10m length of feeder cable.
- Up to 50m of detection cable, or 1x water leak detection probe can be added to the feeder cable
- Up to 50m of false-alarm-resistant water leak detection can be used per interface/zone. Detection cable is made up of 1m, 5m and 10m lengths and with an EOL device. All detection cable connections (and EOL) are made via rapid-fit, waterproof twist/lock connections.
- The ViAC-WLI converts the low voltage DC feed used across AssistCallPro into an AC feed. This means our detection does not corrode in water over time (unlike competitor systems), making
- AquaCall detection maintenance free.
- Status LED shows: Quiescent/normal (green); Active/alarm (blue); Open circuit (steady yellow); Short circuit (flashing yellow).
- Fully monitored system with optional battery backup
| Category Type | Leak detectors |
|---|---|
| Colour | White |
| System Type | Leak Detection |
| Clearance | No |
Specifications
| Height |
86mm |
| Width |
86mm |
| Visible plate depth |
12mm |
| Weight |
60g |
| Material | White polycarbonate |
| Status LED |
Idle, Active, Short, Open Circuit |
| Input | 27V DC via Line Input |
| Output | 2.5VAC via Sensor Output |