Ajax FireProtect 2 SB (Heat) Jeweller - White

In stock
Product Code
106789.136.WH1
SKU
106789.136.WH1

Ajax FireProtect 2 SB (Heat) Jeweller - White

Ajax FireProtect 2 SB Wireless heat detector with sealed batteries giving up to 10 years of operation


DELIVERY

We always aim to same day dispatch on all orders received before 2.30pm.

Read more about our delivery policy

TRADE COUNTER

Firesense also offer the ability to collect your order from our trade counter. 

Read more about our trade counter

FireProtect 2 is a next-gen detector designed for residential fire safety. With two thermistors, the detector quickly reacts to the synthetic materials burning and notifies about danger with a built-in powerful siren and critical alerts from Ajax apps. Thought-out design, mounting, and in-app settings make installation straightforward and quick. Everything meets the most modern fire safety standards.

Attributes
Category Type Detector
Colour White
Detection Heat
IP Rating IP20
System Type Domestic
Clearance No
Write Your Own Review
You're reviewing:Ajax FireProtect 2 SB (Heat) Jeweller - White

Communication

Jeweller communication technology

Proprietary wireless technology for transmission of alarms and events.

Features:

  • Two-way communication.
  • Protection against device spoofing.
  • Block encryption featuring a floating key.
  • Instant notifications.
  • Remote configuration via the Ajax apps
Radio frequency bands

866.0 – 866.5 MHz
868.0 – 868.6 MHz
868.7 – 869.2 MHz
905.0 – 926.5 MHz
915.85 – 926.5 MHz
921.0 – 922.0 MHz

Depends on the region of sale

Maximum effective radiated power (ERP)

up to 20mW

Automatic power control to reduce power consumption and radio interference

Radio signal modulation GFSK
Radio communication range

up to 1,700m

Between the detector and a hub (or radio signal range extender) in an open space

Encryption of radio communication All the data stored and transmitted are protected by block encryption with a floating key
Radio frequency hopping To prevent radio interference and jamming

 

Sensitive elements

Sensors Heat Sensor

 

Dangerous temperature detection

Sensitive element

According to the requirements for Class A1R heat detectors

Requirements of EN54-5 and BS 5446-2 standards

High temperature alarm At temperatures above 64°C
Temperature spike alarm When the temperature rises more than 10°C in 1 minute or less

 

Additional features

In built siren

Volume 85dB at a distance of 3 metres.

Sound notification of alarms. Active until the reason for triggering is eliminated or until the user disables notification

Interconnected fire detectors alarms

Via primary interconnection

If one of the fire detectors in the system detects a threat, it sends an alarm to the hub. Within 20 seconds, the hub initiates an interconnected alarm and sends data to Ajax apps.

via fallback interconnection1

At the same time with notifying the hub, the initiating detector sends an alarm directly to other detectors. All connected detectors activate the buzzer within a minute. It will work even in the worst-case scenario of losing connection with the hub.

1 Fallback interconnected alarm is available only for FireProtect 2 detectors with firmware version 5.59.2.ХХ or later. Devices that support the fallback interconnected alarm are marked on the package with a “Fallback interconnect supported” label.

LED indication

Green is a power indication

A LED indicator on the device enclosure lights up once every 56 seconds. The indication meets the requirements of EN 50291.

Yellow is an indication of malfunctions

A LED indicator on the device enclosure lights up when malfunctions are detected. For example, in the case of discharged batteries, contamination of the smoke chamber, or end of the service life.

Red is an indication of fire alarms

A LED indicator on the device enclosure lights up when the detector registers a fire alarm.

Button on the front panel of the detector In normal mode, when pressed, it starts the smoke chamber test. In the event of an alarm or malfunction, the pressing turns off the detector sound notification.

 

Anti-sabotage protection

Tampering alarm Alerts of attempts to detach the detector from the surface or removing the mounting panel
Protection against spoofing Device authentication
Detection of communication failure

Within 15 minutes. 

The time to detect communication loss depends on the settings for the number of undelivered data packages (specified in the Jeweller or Jeweller/Fibra settings). The polling interval is fixed at 300 seconds.

 

Power supply

Battery

2 non-replaceable lithium batteries

10 years of battery life.

 

Enclosure

Dimensions 44 x 86 x 86mm
Weight 142g
Operating temperature range from 0°C to +50°C
Operating humidity up to 80%
Protection class IP20

 

Colours

Available in Black and White

 

Complete set

Contains

FireProtect 2 RB (Heat) Jeweller

SmartBracket mounting panel

Installation kit

Quick Start Guide